Follow Us:
news
Home > Media > News
Mar 13, 2023
How to solve the high temperature of the fire pump body and the water pressure at the water inlet
1. Check the cooling system of the fire pump, ensure that the cooling system is in good condition, and ensure that the water temperature is kept within the normal range.

2. Check the installation of the fire pump, ensure that the pump is installed correctly, and that the pipe joints are not leaking.

3. Check the water pressure at the water inlet, and adjust the pressure if necessary.

4. Check the motor of the fire pump to ensure that it is operating correctly.

5. Check the pipeline of the fire pump, ensure that the pipeline is clear, there is no blockage, and the water flow is smooth.

6. Reduce the load of the fire pump, reduce the load on the fire pump, and make sure that the pump is not overworked.

7. Increase the water inlet pressure: Increasing the water inlet pressure can help reduce the temperature of the fire pump body. This can be achieved by installing a larger pipe or increasing the size of the pump impeller.

8. Increase the size of the fire pump body: Increasing the size of the fire pump body can help dissipate the heat generated by the pump.

9. Adjust the water flow rate: Adjusting the water flow rate can help reduce the temperature of the fire pump body. This can be done by adjusting the speed of the pump motor or the size of the suction pipe.

10. Install cooling fans: Installing cooling fans can help reduce the temperature of the fire pump body.

11. Insulate the pump body: Insulating the pump body can help reduce the temperature of the fire pump body.


12. Check the water flow rate. If the flow rate is too high, the pump may be overloaded and cause the temperature to increase. Adjust the flow rate to reduce the temperature.

13. Check the inlet water pressure. If the pressure is too high, it can cause the pump to overheat. Install a pressure reducing valve to reduce the pressure.

14. Check the pump impeller. If the impeller is blocked or worn, it can cause the pump to overheat. Clean or replace the impeller to improve the performance.

15. Check the pump motor. If the motor is overloaded, it can cause the pump to overheat. Check the motor and replace or adjust it as needed.

16. Check the pump casing. If the pump casing is not properly sealed, it can cause the pump to overheat. Make sure the casing is properly sealed and vented.

17. Check the cooling system. If the cooling system is not working properly, it can cause the pump to overheat. Check the cooling system and make sure it is functioning properly.
View details
Mar 13, 2023
Fire pump oil change method and how to deal with vibration isolation
Method:

1. Drain the oil from the pump by removing the drain plug.

2. Remove the filter and replace it with a new one.

3. Fill the pump with the new oil until it reaches the recommended level.

4. Replace the drain plug and start the pump to ensure proper oil flow.

5. Check the oil level and adjust if necessary.

How to deal with vibration isolation:

1. Install vibration isolators in the mounting location of the pump to reduce vibration and noise.

2. Check the mounting location for any loose bolts or other components that could cause vibration.

3. Use rubber grommets or other cushioning materials between the pump and its mounting surface.

4. Increase the distance between the pump and the surface it’s mounted on.

5. Make sure the pump has adequate support and is not mounted on an unstable surface.
View details
Mar 13, 2023
Technical requirements for self-inspection of fire pumps and common sense for installation and maintenance of fire pumps
1. Technical requirements for self-inspection of fire pumps

(1) Strictly follow the requirements of national standards and relevant technical documents, and carry out self-inspection of fire pumps in accordance with the operation and maintenance manual.

(2) The fire pump should be tested in accordance with the installation requirements, and the self-inspection shall be carried out in accordance with the requirements of the inspection plan.

(3) Test the power system, control system and protection system of the fire pump, and check whether the wiring is firm and reliable.

(4) Test the performance of the fire pump, including the pressure, flow, vibration, noise and temperature rise.

(5) Check whether the parts of the fire pump are intact and the fastening bolts are firm and reliable.

2. Common sense for installation and maintenance of fire pumps

(1) Fire pumps should be installed in a ventilated and dry place, and the maintenance room should be equipped with the necessary fire protection and monitoring equipment.

(2) The installation and debugging of the fire pump should be carried out by professional and experienced personnel.

(3) After the installation and debugging of the fire pump are completed, the operation and maintenance manual should be read carefully, and the relevant personnel should be trained and qualified before they can be put into use.

(4) The fire pump should be inspected and maintained regularly, and the lubricating oil should be replaced regularly.

(5) The operation and maintenance personnel should be familiar with the operation and maintenance procedures of the fire pump.
View details
Mar 13, 2023
How to start the fire pump and how to deal with the noise

1. Starting the Fire Pump:

a. Ensure that the power switch for the fire pump is in the “on” position.

b. Verify that the pump is receiving power.

c. Open the valve from the water source to the pump.

d. Open the suction valve to the pump.

e. Prime the pump if necessary.

f. Start the fire pump by engaging the motor starter.

2. Dealing with Noise:

a. Install soundproofing material such as rubber vibration dampers or acoustic foam around the fire pump.

b. Install soundproof enclosures around the fire pump.

c. Install sound attenuators in the exhaust stack of the fire pump.

d. Ensure that the fire pump is properly maintained and serviced.

e. Use noise-absorbing absorbent materials, such as mineral wool, to reduce reverberation.

f. Use noise-cancelling ear protection when operating the fire pump.
View details
Mar 09, 2023
What is the control and inspection method of the fire pump
The control and inspection of the fire pump is typically done through a combination of visual inspections, testing, and maintenance. Visual inspections should be done to check for visible signs of damage to the pump and its components, and to make sure that the pump is connected properly and securely. Testing should be done to ensure that the pump is functioning correctly, and that the pressure is adequate for the system requirements. Maintenance should be done to ensure that the pump is running properly and that the system is free of any obstructions or blockages.


1. Periodic Inspection: This type of inspection involves checking the fire pump regularly to ensure that it is in good working condition. This includes checking the electrical connections, fuel lines, and other components to make sure they are in proper working order.

2. Pressure Testing: Pressure testing is a necessary step for any fire pump to ensure that it will be able to deliver the required amount of water during an emergency situation. During this test, the pump is connected to a water supply and pressure gauge, and the system is monitored while the pump is running to ensure that it is delivering the correct amount of pressure.

3. Performance Testing: Performance testing is a more comprehensive test that involves running the fire pump at various speeds and pressures to make sure it is able to deliver the required amount of water. This test is usually done in a laboratory setting, and it is important to make sure the results are accurate.

4. Visual Inspection: Visual inspections are important to ensure that the fire pump is in good working order. This includes checking that all parts are in good condition, that all connections are secure, and that there are no signs of wear or damage.

5. Control:
The fire pump should be operated only when necessary, and should be turned off when not in use. The pump should also be monitored to ensure that it is operating at the correct pressure and flow. Additionally, the system should be checked to make sure that the valves and other components are working properly.
View details
Mar 09, 2023
What to do if the fire pump consumes too much electricity and runs idling
If the fire pump is consuming too much electricity and running idling, the first step is to identify what is causing the problem. It could be due to a problem with the pump, such as a stuck impeller or worn bearings, or it could be a result of poor maintenance. Once the cause has been identified, it can be addressed accordingly. If the issue is a mechanical one, it may need to be serviced or repaired. If the issue is due to poor maintenance, steps must be taken to ensure the pump is serviced and maintained regularly. Additionally, it may be beneficial to install a variable frequency drive (VFD) to help regulate the speed of the pump and reduce electricity consumption.

If the fire pump is consuming too much electricity and running idling, the first step is to identify the cause of the issue. This can include checking for clogged strainers, proper pump control settings, worn impellers, and other mechanical issues. Once the cause of the issue has been identified, it is important to address it as soon as possible. This may involve cleaning, repairing, or replacing parts, as well as adjusting the pump settings. If the issue is due to an electrical issue, it is important to contact a qualified electrician to help identify and fix the problem.

If the fire pump consumes too much electricity and runs idling, the first step should be to check the pump's control panel and settings to ensure that it is running at the correct speed and pressure. If the settings are correct, then the next step would be to inspect the pump itself for any signs of wear and tear, as well as any blockages or obstructions in the system. If the pump is running inefficiently, then it may need to be serviced or replaced. Additionally, it may be necessary to adjust the electrical supply to the pump, to ensure that it is only running when needed.

View details
WhatsApp me